Modbus Register Viewer Modbus

Bit 15 = MSB (top-left) · Bit 0 = LSB (bottom-right) · click to toggle

Decimal —
Hex —
Binary —

Modbus transmits the first register's high byte first. Call the four bytes A B C D in transmission order — so Register 1 carries AB and Register 2 carries CD. The table on the right shows the 32-bit value under each of the four byte-ordering conventions vendors use.

Register 1 (bytes A B)

Register 2 (bytes C D)

Orderint32uint32float (IEEE-754)
ABCD———
CDAB———
BADC———
DCBA———

ABCD is big-endian word + big-endian byte — the Modbus standard's stated ordering. CDAB is the "Modicon byte-swap" form common on legacy gear. BADC swaps bytes within each register; DCBA reverses everything. When a float looks like nonsense at one ordering and plausible at another, the other ordering is the vendor's.

Modbus was the protocol that took me the longest to get a handle on, by far. Hopefully with these tips you won't be spinning your wheels as long as I was.

Modbus is dumb on purpose — a register is just 16 bits, with no metadata about what those bits mean. The vendor's docs are load-bearing.

  • Register addressing offset. "40001" in vendor docs is holding register 0 on the wire — the 4xxxx / 3xxxx / 1xxxx / 0xxxx 5-digit numbering is a documentation convention, not a wire address. Off-by- one bugs live here.
  • Signed vs unsigned. A raw 16-bit value of 65535 is also −1 — same bits, different intent. Use the toggle on the Single Register tab to flip between interpretations.
  • Word / byte order. 32-bit floats and int32s span two registers, and four byte orderings exist in the wild (ABCD / CDAB / BADC / DCBA). The 32-bit Pair tab shows all four side-by-side; pick the one that produces a plausible value.
  • Read FC03 vs FC04. Holding registers (FC03) are read/write; input registers (FC04) are read-only. Write FC06 vs FC16. FC06 writes a single register, FC16 writes many. Wrong FC → illegal function exception.
  • Exception responses set the high bit of FC. A request with FC 0x03 that errors comes back as 0x83 (FC | 0x80) followed by a 1-byte exception code (0x02 = illegal data address, 0x03 = illegal data value, etc.).

A fuller Modbus education page is on the roadmap.

Function codes

FCHexFunction
010x01Read Coils
020x02Read Discrete Inputs
030x03Read Holding Registers
040x04Read Input Registers
050x05Write Single Coil
060x06Write Single Register
150x0FWrite Multiple Coils
160x10Write Multiple Registers

Coils and discrete inputs are 1-bit; holding and input registers are 16-bit — this tool views one of those. Discrete inputs and input registers are read-only; coils and holding registers are read/write.